1www.mastercool.com
COMPACT SUBCOOL/SUPERHEAT
CALCULATOR
TO GET SATURATION TEMPERATURE WHEN
SATURATION PRESSURE IS KNOWN (PT CHART)
1. Press the POWER ( ) button.
2. Use ▲ and ▼ to display the desired refrigerant.
3. Press ENTER.
4. Press any ARROW button to display the pressure, then use
▲ or ▼ to adjust the saturated pressure.
NOTE: To change the pressure quickly, hold the DOWN ARROW
(▼) button.
5. Read the saturated temperature next to the saturated pressure.
NOTE: For refrigerants that have glide, use the SH/SC
button to toggle between Bubble (BBL) and Dew Point (DP) tem-
peratures.
TO GET SUPERHEAT OR SUBCOOL WHEN THE
SATURATION PRESSURE IS KNOWN
To get superheat, use the low (suction) side saturated pressure
and use a tube on the suction side of the compressor for the actual
temperature.
To get subcool, use the high side saturated pressure and use a
tube close to the outlet side of the condenser for the actual
temperature.
1. Press the POWER ( ) button.
2. Use ▲ or ▼ button to display the system’s refrigerant.
3. Press ENTER.
4. Press any ARROW button to display the pressure, then use
▲ OR ▼ to adjust the saturated pressure.
NOTE: To change the pressure quickly, hold the DOWN ARROW
(▼) button.
5. Insert thermocouple clamp plug into side of unit.
6. Clamp thermocouple onto appropriate tube.
7. Press SH/SC to toggle between superheat or subcool
temperature.
8. Once the temperature has stabilized, read the superheat or
subcool temperature.
NOTE: The unit will not display a negative superheat or subcool
temperature. It will display -- instead. Check the side you are read-
ing your pressure on and the location of the thermocouple clamp.
ADDITIONAL FUNCTIONS
Hold Function
To freeze the temperature reading from the thermocouple on the
screen, press HOLD.
Vedere la pagina 0
1 2 3 4

Sommario

Pagina 1 - CALCULATOR

1www.mastercool.comCOMPACT SUBCOOL/SUPERHEAT CALCULATOR TO GET SATURATION TEMPERATURE WHEN SATURATION PRESSURE IS KNOWN (PT CHART)1. Press the POWER

Pagina 2 - Prepare the 52246

2 www.mastercool.comHOLD will blink under the thermocouple temperature reading. The pressure values can still be changed and the superheat or subcool

Pagina 3 - Install the Refrigerants

3www.mastercool.com Figure 13. Remove the back of the unit taking care that

Pagina 4 - USA: PH (973) 252-9119